Kinco CV100 Frequency inverter - Modbus
Frequency inverter
4T : triphase 380V~440V – 50Hz/60Hz // 2S : singlephase 200V~240V
Switching frequency: 6 kHz
Output frequency: 0 - 300Hz
Frequency control: Digital, analog voltage/current
1 RS485 Modbus port
1 reference voltage output 10V - 5mA
2 analog inputs -10~+10V or 0mA~20mA
5 optocoupled multifunction digital inputs
2 analog outputs 0~10V or 0/4~20mA
1 optocoupled open collector output 30V - 50mA
1 relay output, 250VAC - 2A, 30VDC - 1A
1 power supply output +24V - 200 mA
Features
Power : 200W - 400W - 750W - 1500W - 2200W
Carrier Frequency up to 15kHz
Output Frequency : 0 - 300Hz
Auto torque boost and auto slip compensation function
Built-in PID control
Auto standbye function
Wall mounting
1 RS485 Modbus port
1 10v reference voltage output
2 analog inputs -10~+10V
5 digital multi-function input, Optocoupler isolation
2 analog output 0~10V or 0/4~20mA
1 optocoupled output, open collector 30V - 50mA
1 relay output, 250VAC - 2A, 30VDC - 1A
1 power supply output +24V - 200 mA
External dimensions <= 1500W :
W : 85 mm
H : 142 mm
D : 122 mm
Weight: 0.8 kg
External dimensions 2200W :
W: 101 mm
H : 152 mm
D : 127 mm
Weight : 1 kg
Features
Item | Description | |
---|---|---|
Input | Rated voltage and frequency | 4T : triphase 380V~440V – 50Hz/60Hz // 2S : singlephase 200V~240V |
| Allowable voltage range | 4T : 320V~460V // 2S : 180V~260V - Voltage unbalancedness <3 % - Frequency +-5 % |
Output | Rated Voltage | 0~Rated input voltage |
Frequency | 0Hz~300Hz | |
Overload capacity | Type G : 150 % 1 mn – 180 % 10 s | |
Controle method | Mode | V/F |
Starting torque | Auto torque rising | |
Frequency accuracy | Digital setting : max. frequency x +- 0.01% – Analog setting : max. frequency x +-0.2 % | |
Frequency resolution | Digital setting : 0.01Hz – Analog setting : max. frequency x 0.05 % | |
Torque boost | Manual torque boost : 0% ~ 30.0 % | |
V/F patterns | 4 patterns : 1 V/F curve mode set by user and 3 kinds of torque- derating modes (2.0 power - 1.7 power - 1.2 power) | |
Acc/Dec curves | Linear/deceleration. Four kinds of acceleration/deceleration time | |
Auto current limit | Limit current durinf operation automatically to prevent | |
Operation command | Keypad setting – Terminal setting – Communication setting | Integrated screen - Inputs - Modbus |
Frequency command | Digital setting – analog voltage setting – analog current setting | |
Auxiliary frequency setting | Implement flexible auxiliary frequency trim and frequency synthesis | |
Analog output | 2 channel analog output (0/4~20mA or 0/2~10V) | |
Protection functions | | Overcurrent protection - overvoltage protection – undervoltage protection – overheat protection – overload protection – missing phase protection (selectable) and so on |
Environnement | Use | Indoor - installed in the environnement free from direct sunlight – dust – corrosive gas – combustible gas – oil mist – steam and drip |
Altitude | Derated above 1000m – the rated output current shall be decreased by 10% for every rise of 1000m | |
Ambient temperature | -10°C~40°C - derated at 40°C~50°C | |
Humidity | 5%~95%RH – non-condensing | |
Vibration | Less than 5.9m/s2 (0.6g) | |
Storage temperature | -40°C~70°C | |
Structure | Protection class | IP20 |
Cooling method | Air cooling with fan control | |
Installation method | Wall mounting | |
Efficiency | ≥ 93 % | |
Connections
Category | Marking | Description | |
---|---|---|---|
GND for the shield | PE | GND for the shield | |
Power Supply | +10 | +10V power supply | Reference Voltage +10V – 5mA |
OP | +24V power supply | for small equipments 24V 200mA max. | |
Communication | RS+ / RS- | port RS485 | Use twisted-pair or shield cable |
Analog input | AI1 and AI2 | Analog single-ended | Analog voltage or current input – mode selected by jumpers AI1/AI2 (Reference ground : COM) ) – Voltage range -10V~+10V (Input resistor 45kOhm) Resolution 1/4000 – Current range 0mA~20mA Resolution 1/2000 (jumper select) |
Analog output | A01 and AO2 | | Providing analog voltage or current selected by jumper AO1/AO2 – The default setting is output voltage refer to to the function code A6.28/A6.29 (Reference ground : COM) - Voltage range 0V~10V – Current range 0/4mA~20mA |
Multifonction input terminal | X1~X5 | | Can be defined as multi-function digital input terminal – Refer to description of function code A6.00~A6.04 (A6 group) – Optocoupler isolation input – input resistor 3.3kOhm – Input voltage range of X1~X5 : 2~30V |
Multifonction output terminal | Y1 | Bi-direction open collector output | Can be defined as multi-function digital ouput terminal – Refer to description of function code A6.00~A6.04/A6.14 (A6 group) – Optocoupler isolation output – Max. working voltage : 30Vmax. Current 50mA |
Common port | COM | | Common port of 24V power supply. Cooperate with other terminals. |
Specifications
Drive power | 200 W or 400 W or 750 W or 1500 W or 2200 W |
Brand | Kinco |
Voltage | 230 VAC |
Inputs | 5 |
Analog inputs | 2 |
Analog outputs | 2 |
Interface | Modbus RS485 |